MAQ20-JTC

Analog Input Module; Type J Thermocouple, 8-ch

MAQ20-JTC
Analog Input Module; Type J Thermocouple, 8-ch

Product Availability:
  • Usually stock to 3-5 weeks. Contact Customer Service for current lead times.

Description

The MAQ20 thermocouple analog input modules have 8 differential input channels. Separate models are offered for interfacing to Type J, Type K, Type T and Types R and S thermocouples. Cold Junction Compensation uses four internal sensors resulting in industry leading measurement accuracy in any system configuration and over the entire system operating temperature range. All channels are individually configurable for range, alarm limits, and averaging to match the most demanding applications. High, Low, High-High and Low- Low alarms provide essential monitoring and warning functions to ensure optimum process flow and fail-safe operation. Hardware low-pass filtering in each channel provides rejection of 50 and 60Hz line frequencies. Field I/O connections are made through spring cage terminal blocks with four positions provided for the termination of wiring shields.

Input-to-bus isolation is a robust 1500Vrms and each individual channel is protected up to 150Vrms continuous overload in case of inadvertent wiring errors. Overloaded channels do not adversely affect other channels in the module, thereby preserving data integrity.

Channels in a module can be selectively enabled for scanning. All channels are enabled by default; however, non-used channels can be disabled to increase the sampling rate of enabled channels.

Input ranges are selectable on a per-channel basis. The MAQ20-JTC, -KTC, -TTC and -RSTC modules have two to four user selectable input ranges, depending on the model. Over-range and under-range up to 2% beyond the specified input values is allowed. Sensor linearization is performed in the module, and accuracy is guaranteed to ±f.s.

Features

  • Differential Input Channels
  • Interface to Types J, K, T , R and S Thermocouples
  • All Channels Individually Configurable for Range, Alarms, Averaging
  • 1500Vrms Input-to-Bus Isolation
  • Each Channel Protected up to 150Vrms Continuous Overload
  • Selective Enabling of Module Channels for Scanning
  • UL/cUL (Class I, Division 2, Groups A, B, C, D)

Block Diagram

Certifications

Specifications

  • Sensor Type Thermocouple
  • Input Range 8-ch., Type JTC, Differential Input –100°C to +760°C (Default), –100°C to +393°C, –100°C to +199°C
  • Output Range
  • Communication Via MAQ20-COM2 / -COM4
  • Protocol Modbus TCP/IP or RTU
  • Mechanical Format DIN rail mounting
  • Isolation Voltage 1500Vrms
  • Accuracy ±0.06% span
  • Linearity ±0.035% span
  • Cold Junction Compensation ±0.25°C at +25°C, ±1.0°C at –40°C to +85°C
  • Supply Voltage / Current 30mA
  • Input Voltage Protection 150Vrms max
  • Output Voltage Protection
  • Bandwidth, -3dB 3Hz
  • Scan / Update Rate 200 Ch/s
  • NMR (60 Hz) Rejection 26dB at 50/60Hz
  • Output
  • Excitation Voltage
  • Dimensions 4.51” x 0.60” x 3.26”
  • Operating Temperature –40°C to +85°C
  • Weight 87 grams (3.07 ounces)

Accessories

MAQ20-5B26-0.3
IDC26-to-20 pos screw term Transition Cable, 0.3m (11.8”) long View
MAQ20-5B26-0.6
IDC26-to-20 pos screw term Transition Cable, 0.6m (23.6”) long View
MAQ20-5B26-01
IDC26-to-20 pos screw term Transition Cable, 1.0m (39.4”) long View
MAQ20-8B25-0.3
DB25-to-20pos. screw terminal cable, 1 foot (305 cm) long View
MAQ20-8B25-0.6
DB25-to-20pos. screw terminal cable, 2 foot (610 cm) long View
MAQ20-8B25-01
DB25-to-20pos. screw terminal cable, 3 feet (915 cm) long View
MAQ20-PWR3
Boost Power Supply Module, 5VDC at 3A Output View
MAQ20-XCA-01
Backbone Expansion Cable; 1 meter View
MAQ20-XCA-02
Backbone Expansion Cable; 2 meter View
MAQ20-XTB03
MAQ20 terminal block, 3 positions View
MAQ20-XTB20
MAQ20 terminal block, 20 positions View

Competitive Cross-Reference

  • No cross reference is available.
View Dataforth cross-reference data.
The information available through this competitive cross reference guide are based upon product catalog information obtained from a variety of sources. The competitive cross reference information is being provided to you free of charge for your use. While Dataforth Corp has used reasonable efforts to ensure data accuracy, Dataforth Corp does not guarantee that it is error-free, nor does Dataforth Corp make any other representation, warranty or guarantee that the information is accurate, correct, reliable or up-to-date. Dataforth Corp expressly disclaims all implied warranties regarding this information, including but not limited to any implied warranties of merchantability or fitness for a particular purpose.

This information is provided only as a convenience on an "as is" basis and Dataforth Corp. or its representatives or distributors are not responsible for any incorrect, inaccurate, or incomplete information. You are solely responsible for (1) selecting the appropriate Dataforth products for your application, (2) designing, validating and testing your application, and (3) ensuring your application meets applicable standards, and any other safety, security, or other requirements.

FAQ

Was this content helpful?
Thank you for your feedback!
Menu
Top